D-100-P1 Flow Display Manual 05/14 - 0660-3 / 18343

Page 8

Powered Pulse:

This type of output refers to a pulse which has an associated voltage with it (see Fig. 2).
Set the selector switch, S1 to Pwrd Pulse. The allowable voltage range is 5-24 VDC. The
input impedance is set at the factory to be 11 KOHM via the impedance selector jumper
(J1, see Fig. 1). A lower impedance, 3 KOHM can be selected if required by the instrument
providing the pulse output. Consult the instrument manufacturer or ONICON if you are
uncertain as to the proper jumper selection.

Fig. 2

Open Collector (Sourcing):

This type of output refers to an open Collector Switch configured for a sourcing function
(see Fig. 3). Set the selector switch, S1 to SRC. The switch must be rated for at least 20mA
at 20VDC.

Fig. 3

Di3 In (+)

Di3 In (-)

Di3 In (+)

Di3 In (-)