OnLine Power Mini Power Wave User Manual

Page 22

Advertising
background image

6005-100 Rev A

13

Settings

LCD display

Explanation

Selection

Factory

default

208/220/230/240 V

230V

Output Volt.Setting

O/P V Setting

Select Nominal Voltage

100/110/115/120/127

V

120V

Input/Frequency

I/P F Setting

Select input frequency range

when UPS goes into free run

mode

±2%

±5%

±7%

±5%

Input/Bypass

Voltage

I/P Bypass Set

Select Input Voltage range

when bypass is available

±10%

+10/-15%

+15/-20%

+10/-15%

Free Run Mode

Free Run Set

Select if UPS can run in Free

run mode (unsynchronized)

ON/OFF

ON

Bypass
Enable/Disable at Free run
mode

Bypass disable

If Enable is chosen, the UPS

can go to bypass when

unsynchronized.

Disable/Enable

Disable

He mode Setting

HE Mode Set

Select if UPS runs in high

efficiency mode

ON/OFF

OFF

Force Manual
Bypass

Manual bypass

Permanently force UPS to

bypass. For service only.**

ON/OFF

OFF

Management of
Load groups

Outlet Setting

You can put the two load groups

on and off form front panel

1 ON & 2 ON

1 OFF & 2 ON

1OFF & 2 OFF

1 ON & 2 OFF

Both load

segments ON

Do Battery Test

Battery Test

Detect battery is normal or not.

Silence Function

Silence Set

Enable or disable silence

function

ON/OFF

OFF

Number of
External battery Packs

Bat Cabinet Set

This setting is needed

For UPS to predict

Backup time

0 (only internal

batteries)

1(one external

cabinet)

2 (two external

cabinets)

0

Site wiring alarm

Sit Fault Set

You can enable or disable the

site wiring alarm

Enable /Disable

Disable

Select Language

Language

Select load language

English, German,

French, Spanish,

Italian.

English

Set Generator Mode

Generator

Set unit in generator mode.

***

ON/OFF

OFF

Set RS232 communication RS232 Control

Set RS232 communication

enable or disable

Enable/Disable

Enable

Advertising
This manual is related to the following products: