OnLine Power Mini Power Wave User Manual

Page 24

Advertising
background image

6005-100 Rev A

15

7. Trouble Shooting

Displayed on
LCD

Audible Alarm

Alarm Description

What You Should Do

Output Overload

Two Beeps per second

The UPS is overloaded

(in Line Mode). Your

equipment needs more

power than the UPS can

provide. The UPS

operates in bypass.

Shut off the least important

equipment connected to the

UPS. If this solves the overload

problem, the UPS will switch

from bypass back to normal

operation.

Battery Test

No Beeps

The UPS is doing a
battery test.

No action needed. The UPS will
return to normal operation when
it successfully completes the
battery test.

Over-Charge

Constant beep

Batteries are

overcharged.

Turn off protected loads. Turn

off UPS and call your local

dealer

Low Battery

2 beeps every

5seconds

The unit is operating on

Battery Power and will

shut down soon due to

very low battery voltage

The unit will restart

Automatically when acceptable

power returns.

On-Battery

Once every 5 seconds The unit is operating on

Battery Power.

Save your data and perform a

controlled shutdown.

Charger Failure

Constant beep

Charger has failed.

Phone the local dealer

Over-Temperature Constant beep

High ambient

Temperature.

Make sure the unit

s fans and

vent holes are not blocked, and

make sure the ambient

surrounding temperature is not

above 40 degree C. If these

conditions did not solve the

problem, call your service

representative.

Output Short

Constant beep

Output short circuit

Call the Local dealer

High output

Voltage

Constant beep

High output voltage

Call the Local dealer

Low Output

Voltage

Constant beep

Low output voltage

Call the Local dealer

Bus Fault

2 Beeps per second

High internal DC bus

Voltage.

Turn off protected loads. Turn

off UPS and call your local

dealer

Site wiring Fault

1 Beep per second

Voltage detected

Between Neutral and

Ground

UPS mains connector polarity

Wrong. Rotate the connector

(Schuko). UPS installed to

mains supply without ground.

See page 15 on how to disable

the Site wiring alarm

Line abnormal

1 Beep per second

Wrong AC Line backed

up during auto restart