OnLine Power

6002-034 REV. C

A-1

APPENDIX A - SPECIFICATIONS

CONSTANT POWER 6

CONSTANT POWER 3

MINI-POWER

Sizes

3, 5, 8, 10, 15 kVA

1, 1.5, 2, 2.5, and 3 kVA

1, 1.5, and 2 kVA

Input Voltage

120 or 208/220/240 or 480 VAC

120, or 208, or 240 VAC

Output Voltage

120 or 120/240 VAC

Frequency

60 Hz +5%

Transformer Type

Single Phase Computer-Grade, Dual-Shielded, Isolation Transformer

Transformer Impedance

3 to 5% maximum

Efficiency

96% minimum

Load Power Factor

0.3 Leading or Lagging to Unity

Harmonic Distortion

3% Individual, 5% Total at Switching

Audible Noise

<35 dB. Measured on Response Curve ”A”

Typical Noise Rejection

Common Mode: -120 dB

Normal Mode: -60 dB/decade

Input Voltage Regulation
Range

+10% to -26% of nominal

+7% to -23% of nominal

Output Voltage Regulation
Range

+3% Typical

+4% All Line-Load Cond.

+5%

Cooling

Convection

Response Time

1 Cycle Typical

Loading Rating

Continuous, Regardless of Load/Line Conditions

Overall Inrush Rating

200% for 10 seconds; 1000% for 1 Cycle

Environmental

Operating Temperature

32

°

F (0

°

C) to 104

°

F (40

°

C)

Storage Temperature

-4

°

F (-20

°

C) to 140

°

F (60

°

C)

Operating Humidity

10 to 95% Non-Condensing

Dimensions

Height

19.5” (49.5 cm)

10.5” (26.8 cm)

1

2” (30 cm)

Width

14.5” (36.8 cm)

11” (28.2 cm)

6.5” (17 cm)

Depth

25.5” (64.8 cm)

15.5” (39.7 cm)

12” (30 cm)