Sensor, Sensor overview, Technical guide – Orion System CO2 Sensor v.1 User Manual

Page 3: 3overview, Features, Environmental requirements

Advertising
background image

Technical Guide

CO

2

SENSOR

3

Overview

The Wall Mounted Space CO

2

Sensor (OE256-01) is used for monitor-

ing room CO

2

levels and is designed for permanent wall mounting in

the conditioned space

. It connects to the VCM-X E-BUS Controller

(OE332-23E-VCMX) or

RNE Controller (OE332-23E-RNE)

by using

TSDRSC modular prefabricated cable with RJ-45 connectors. It can be
daisy-chained with the Digital Room Sensor (OE217-00 or OE217-01)
or wired separately from the Orion Space Temperature Sensor (OE210,
OE211, OE212, or OE213) for applications requiring both a room CO

2

sensor and room temperature sensor.

See Figure 1 for dimensions.

The OE256-02 Duct Mounted

CO

2

Sensor is comprised of the OE256-01

CO

2

Sensor and the WattMaster Aspiration Box Assembly. It is used for

sensing the current CO

2

level in the HVAC unit’s return air stream. It is

designed to be mounted in the return air of the HVAC unit and uses its
integral aspiration box to sample the CO

2

level in the duct.

Some typical applications are:



Controlling ventilation in a building where the occupancy

varies

frequently



Controlling ventilation to ensure excess outdoor air is not

causing energy waste



Ensuring good air distribution throughout building zones



Demand Control Ventilation

Sensor Overview

Features

The CO

2

Sensor provides the following:



Uses the patented dual beam Non-Dispersive Infrared

(NDIR)

technology



A very accurate and stable sensor guaranteed to maintain

its accuracy due to infrared self-calibration feature of sensor



Sensor accuracy of +/- 50 ppm @ 1000 ppm or 2% of the

measured

value



Annual drift of +/- 2 ppm per year



Measurement range of 0 to 2000 ppm



LED under front cover shows active CO

2

sensing



Addressable based on function within the system

Figure 1: Wall Mounted CO

2

Sensor Dimensions

Environmental Requirements

The CO

2

Sensor needs to be installed in an environment that can main-

tain a temperature range between 14°F and 122°F and a humidity range
between 5% and 95% RH (non-condensing).

Advertising
This manual is related to the following products: