Wall mounted e-bus co, Sensor, Sensor overview – Orion System OE256-05 Wall Mounted v.1 User Manual

Page 3: Technical guide, 3overview, Features, Environmental requirements

Advertising
background image

Technical Guide

WALL MOUNTED E-BUS CO

2

SENSOR

3

Overview

The OE256-05 Wall Mounted E-BUS CO

2

Sensor is used for monitoring

space CO

2

levels and is designed for permanent wall mounting in the

conditioned space

. It connects to the VCB-X Controller (OE335-23-

VCBX)

and VCC-X Controller (OE338-26B-VCCX)

using an EBC

E-BUS Expansion Cable. It can be daisy-chained with the E-BUS
Digital Room Sensor (OE217-02, OE217-03, OE217-04) for applica-
tions requiring both a space CO

2

sensor and space temperature sensor.

See Figure 1 for dimensions.

The OE256-07 E-BUS Duct Mounted

CO

2

Sensor with Remote Pickup

utilizes an aspiration box. It is used for sensing the current CO

2

level in

the HVAC unit’s return air stream. It is designed to be mounted in the
return air duct of the HVAC unit and uses its integral aspiration box to
sample the CO

2

level in the duct.

This technical guide provides information for the Wall Mounted E-BUS
CO

2

Sensor only, for more information regarding the Duct Mounted E-

BUS CO

2

Sensor, please see the OE256-07 Duct Mounted E-BUS CO

2

Sensor Technical Guide.

Some typical applications are:



Controlling ventilation in a building where the occupancy

varies

frequently



Controlling ventilation to ensure excess outdoor air is not

causing energy waste



Ensuring good air distribution throughout building zones

Sensor Overview

Features

The CO

2

Sensor provides the following:



Uses the patented dual beam Non-Dispersive Infrared

(NDIR)

technology



A very accurate and stable sensor guaranteed to maintain

its accuracy due to infrared self-calibration feature of sensor



Sensor accuracy of +/- 50 ppm @ 1000 ppm or 2% of the

measured

value



Annual drift of +/- 2 ppm per year



Measurement range of 0 to 2000 ppm



LED under front cover shows active CO

2

sensing



Addressable based on function within the system

4.54

2.80

0.96

0.80

Figure 1: Wall Mounted E-BUS CO

2

Sensor

Dimensions

Environmental Requirements

The E-BUS CO

2

Sensor needs to be installed in an environment that can

maintain a temperature range between 14°F and 122°F and a humidity
range between 5% and 95% RH (non-condensing).