Wall mounted e-bus co, Sensor, Wall mounted space co – Orion System OE256-05 Wall Mounted v.1 User Manual

Page 4: Sensor wiring to vcb-x controller, Technical guide 4, Wall mounting, Wiring to the vcb-x controller, Figure 2: wall mounted space e-bus co, Optional mounting plate, Ebc e-bus cable

Advertising
background image

WALL MOUNTED E-BUS CO

2

SENSOR

Technical Guide

4

Figure 2: Wall Mounted Space E-BUS CO

2

Sensor & Digital Room Sensor Wiring for VCB-X Controller

OE256-05

Wall Mounted E-BUS

CO Sensor

2

EBC E-BUS Cable

EBC E-BUS Cable

Display

Override

OVERRIDE

ALARM

NOTE: Mount Both
Sensors At Least
5 Feet Above Floor.
The Digital Room
Sensor Connects To
The

Sensor.

CO

2

OE217-02, OE217-03, OE217-04

E-BUS Digital Room Sensor

VCB-X Controller

MADE IN USA

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY 6

RELAY
COMMON

24 VAC POWER

ONLY

WARNING!

POLARITY MUST

BE OBSERVED

OR THE

CONTROLLER

WILL BE

DAMAGED

www.aaon.com

www.orioncontrols.com

VCX CONTROLLER

Orion No.:OE335-23-VCX

ANALOG INPUTS

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

BI1

BI2

BI3

B4

AO1

AO2

AO3

TR1

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= DCT (DIGITAL COMP. DISCHARGE TEMPERATURE SENSOR)
= SPACE TEMPERATURE SLIDE OFFSET

= EMERGENCY SHUTDOWN
= PROOF OF FLOW
= DIRTY FILTER
= REMOTE OCCUPIED OR COIL TEMPERATURE SWITCH

= FAN VFD
= ECONOMIZER
= SCR OR MODULATING HW HEATING

= DIGITAL COMP. UNLOADER (24 VAC & UNLOAD TERMINALS)

BINARY INPUTS

ANALOG OUTPUTS

TRIAC OUTPUT

I

LED BLINK CODES

LED NAME

STATUS1 STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

OUTPUT FORCE ACTIVE

0

6

WattMaster Label

#LB102093-01-A

Rev.: 1C

E-BUS

EXPANSION

E-BUS

EXPANSION

24 VAC

INPUT

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

24 VAC POWER

ONLY

WARNING!

POLARITY MUST

BE OBSERVED

OR THE

CONTROLLER

WILL BE

DAMAGED

www.aaon.com

www.orioncontrols.com

VCB-X CONTROLLER

Orion No.:OE335-23-VCBX-A

AAON No.:

V04740

ANALOG INPUTS

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

BI1

BI2

BI3

Bi4

AO1

AO2

AO3

TR1

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= DCT (DIGITAL COMP. DISCHARGE TEMPERATURE SENSOR)
= SPACE TEMPERATURE SLIDE OFFSET

= EMERGENCY SHUTDOWN
= PROOF OF FLOW
= DIRTY FILTER

= COIL TEMPERATURE SWITCH

= FAN VFD
= ECONOMIZER
= SCR OR MODULATING HW HEATING

= DIGITAL COMP. UNLOADER

(24 VAC & UNLOAD TERMINALS)

BINARY INPUTS

G OUTPUTS

TRIAC OUTPUT

ANALO

STATUS LED BLINK CODES

LED NAME

STATUS1 STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

AIRFLOW SENSOR FAIL

7

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

OUTPUT FORCE ACTIVE

0

6

WattMaster Label

#LB102093-01-A

Rev.: 1A

E-BUS

EXPANSION

E-BUS

EXPANSION

+24

VAC

GN

D

ALERT LED BLINK CODES BLINKS

NORMAL OPERATION

0

MISSING OR SHORTED
DISCHARGE TEMP. SENSOR

1

IN 30 MIN. CUTOFF PERIOD

3

IN HIGH TEMP. CUTOFF

4

COMPRESSOR LOCKED OUT

6

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY 6

RELAY
COMMON

Wall Mounted Space CO

2

Sensor Wiring to VCB-X Controller

Wall Mounting

The OE256-05 Wall Mounted E-BUS CO

2

Sensor utilizes a sub-base

mounting plate with a modular phone jack providing quick and easy
mounting and wiring. The wall-mounted sensor’s sub-base is compat-
ible with standard junction boxes. A locking screw secures the assembly
to the wall.

Optional Mounting Plate

Included with the Digital Room Sensor is a mounting plate that
can be used, if necessary, to cover the sensor sheet rock opening.
This mounting plate screws onto the back of the housing base.
The mounting plate is then mounted and covers the recessed space
in the wall. A locking screw secures the sensor to the wall. See
Figure 6, page 7 for dimensions.

Wiring to the VCB-X Controller

The OE256-05 Wall Mounted E-BUS CO

2

Sensor connects to the

VCB-X or VCC-X Controller with an EBC E-BUS expansion cable. It
can be daisy-chained

with the Digital Room Sensor (OE217-02, OE217-

03, OE217-04) for applications requiring both a space CO

2

sensor and

space temperature sensor.

Refer to Figure 2 for instructions (VCB-X

Controller shown).