WALL MOUNTED E-BUS CO

2

SENSOR

Technical Guide

6

Troubleshooting

Using LEDs to Troubleshoot

LEDs are available for troubleshooting the CO

2

Sensor. The LEDs are

ON when Dipswitch 8 is on. The LEDs are off when Dipswitch 8 is off.
The Front LED is visible through the front cover of the CO

2

Sensor. See

Figure 5 for location. The other LEDs are located on the Sensor’s board
and are only visible by taking the device off the wall and removing the
back cover. See Figure 4 for locations.

Front LED

When the LEDs are turned on, a green LED will be visible through the
front plastic cover of the CO

2

sensor. See Figure 5. The Front LED

will blink whenever a CO

2

sample is taken. A sample is taken every

30 seconds.

STATUS LED

Initially, the STATUS LED blinks fast for 30 seconds. It then stays on
and blinks the board address whenever a CO

2

sample is taken. A CO

2

sample is taken once every 30 seconds.

COMM LED

The COMM LED blinks on whenever communications are sensed.

Altitude Correction

Altitude correction can be confi gured using Prism 2 software installed
on a computer. The altitude can be confi gured at a value of 0-15,000
feet. The default is 500 feet.

TB1 Terminal Block (CO

2

Reading)

The TB1 terminal block should only be used to test the sensor when the
sensor cable is plugged into the controller and the sensor and controller
are powered up. Directions: Set the meter for DC volts and connect
the GND probe to the GND terminal and the + probe to the CO

2

0-5

terminal. Look at the output voltage and record it. Multiply the voltage
times 400. The value should match the CO

2

as read on the System Man-

ager TS, Modular System Manager, Modular Service Tool, or Prism. If
the signal doesn’t match the sensor reading, call WattMaster Controls
for a replacement.