Installation

NOTICE!

Installation should only be performed by

authorised specialists.

Unit installation

The unit is mounted on four threaded rods with the

cover face down. Take into account the ceiling grid

and any other installations.

1.

Use the dimensions of the ceiling cassette to

mark the fixing points for the threaded rods

on structural parts approved to support the

static load, and above the suspended ceiling.

(Fig. 26).

2.

Fit the indoor unit onto the threaded rods and

use the lower nuts to level the unit (Fig. 27).

3.

Ensure a clearance of 35 mm from the

ceiling. Connect the refrigerant pipes, elec-

trical cables and condensation pipe to the

indoor unit as described below.

4.

Check that the unit is level.

5.

The final task is to tighten the counternuts

and attach the cover.

522

522

Fig. 26: Unit attachment (MXD 202-522)

1

1

A

B

Fig. 27: Hooking in the unit (MXD 202-522)

1: Structural component

A: Minimum 35 mm

B: 265 mm

A

Fig. 28: Fasten the unit

A: Distance A

MXD 262-522

Distance A

70 mm

Suspension

545 mm x 525 mm

23