Fault indication by flashing code

LED

OPERA-

TION

(green)

LED

TIMER

(orange)

LED

DEF/

FAN

(red)

LED

ALARM

(red)

OU Dis-

play

Cause

Required action

on

on

Normal operation, no

faults: heating mode

-

on

Normal operation, no

faults: cooling-, recircu-

lating air or automatic

mode

-

on

Normal operation, no

faults: On timer pro-

grammed

-

on

on

Normal operation, no

faults: Off timer pro-

grammed

-

flashes

-

Probe recirculating air

defective/actuated

Check resistance on

sensor

flashes

-

Probe vaporizer defec-

tive/actuated

Check resistance on

sensor

flashes

E7

Communication error

between PCBs OU & IU

Check electrical connec-

tion leads

flashes

flashes

E0

EEPROM error

Check EEPROM

flashes

on

-

Shutdown inverter

module

-

flashes

-

Liquid level switch con-

densate pump defective/

actuated

Contact specialist dealer

flashes

on

E4

Probe outdoor tempera-

ture OU actuated

Check resistance and

temperature on sensor

flashes

on

on

E5

Surge voltage on outdoor

unit

Check power supply

flashes

on

P0

Overtemperature com-

pressor

Allow to cool compressor

flashes

on

on

-

Mode conflict:

Set unit with fault display

on refrigerators and

other appliances to

heating mode

Priority heating: program

all unitss on cooling

mode / de-energize

flashes

flashes

flashes

P3

Power consumption on

OU too high

Check power consump-

tion

For further fault diagnosis and troubleshooting s. corresponding user manual outer part.