Mounting the control unit, Mounting the sensors – REMKO ATR-3 User Manual

Page 12

Advertising
background image

12

The temperature control must be mounted outside of heavily trafficked
areas in a place that is easily accessible for making settings. If it is gen-
erally accessible, it must be protected against unauthorised use.

The supplied drilling stencil makes the
temperature control easier to install. The
attachment points can also be found in
the drawing to the left. Mounting materi-
als must be supplied by the customer.
After the unit has been mounted, the in-
stalled lines are inserted from below into
the housing through the supplied screw
attachments once the lead-throughs
have been removed.

Mounting the Control Unit

Mounting the Sensors

2 KTY temperature sensors are required to measure the differential tem-
perature.

The upper temperature sensor
is installed in the ceiling area
and should have a minimum dis-
tance of 3 m to the ceiling fan.
Do not mount the sensor close
to air intake and outlet ducts.
The lower temperature sensor is
attached at a height of approx.
1.5 m and should not be in the
direct vicinity of the air current
from the ceiling fan.

If the temperature sensor is mounted on a cold, outside wall, an insula-
tion panel must be installed between the wall and the sensor by the cus-
tomer.
The temperature sensors are connected to the temperature control with
2-wire lines. The connections are polarised. Make sure that the terminals
are assigned correctly: “LOWER” temperature sensor terminals 5 + 6;
“UPPER” temperature sensor terminals 6 + 7.
Specifications for checking proper operation of the KTY temperature
sensor:

Þ

at 20°C: resistance value approx. 1879 Ω

Þ

at 30°C: resistance value approx. 2035 Ω

min. 3 m

Fan

1,5...2,0 m

Temperature
sensor, lower

Temperature
sensor, upper

99

99

145

Figures in mm