Technical Data

Temperature range
(Day and night temperature)

0 to 30°C, adjustable; to 5 to 30°C
can be limited by an internal setting

Temperature difference dT

1 to 10K, adjustable

Proportional control Xp

1 to 5K, adjustable

Heating

-1 to -10K, distance from target value
adjustable

Clock timer

Electronic weekly clock timer,
power reserve clock approx. 10 minutes,
program is permanently saved

Sensor

KTY semi-conductor sensors (polarised)

Operating current

230V AC, +10%, -15%

Internal consumption

approx. 5 VA

Outputs: Fan output

approx. 80 to 230 V gradually increasing
current (phase control) for the fan

Heating relay

isolated contact (shutter)

Additional relay

isolated contact (two-way contact)
(switches on/off with phase control)

Analog output

0-10V, parallel to the phase control (Xp)

Max. line load currents

6,3A, 230V AC fan on the phase control
10 (4)A, 250V AC heating relay
2 (2)A, 250V AC additional relay
1 mA max. on the analog output (0...10 V)

Housing Dimensions

242 x 185 x 115 mm (W x H x D)

Attachment

wall-mounted

Protection type

IP 54 (protected from spraying water)

Protection class Il in accordance with DIN EN 60335-1

Weight

approx. 1500 g