SERVICE DIAGNOSIS

SYMPTOM

POSSIBLE CAUSE

SUGGESTED CORRECTION

Wet ice

Ambient temperature too high

Move unit to cooler location

High water level in the freezer

Lower to approx. 20mm below ice spout

Faulty compressor

Replace

Machine runs but makes no ice

Water not entering in the freezer

Air lock in feed line to freezer.

Clogged feed line to freezer. Clean it

Gear stripped

Check and repair

Moisture in the system

Purge, replace drier and re-charge

Water leaks

Water seal leaking

Replace water seal

Water feed line to freezer leaking

Check and fasten hose clamp

Float valve not closing

Check and adjust float valve setting

screw

Excessive noise or chattering

Mineral or scale deposit on auger

Remove and manually polish auger and

inner freezer walls and inner walls of

freezer barrel using emery paper

Low suction pressure

Add refrigerant to increase suction

pressure

Water feed line to freezer clogged

Vent and clean it

Low water level into freezer

Adjust to approx. 20 mm below ice

spout

Gear motor noise

Worn rotor bearings

Check and replace

Shortage or poor lubricant in gear case

Check for proper lubricant level by

opening gear case.

Top of gears must be covered with

lubricant

Gear case bearings and gear racers worn

out

Check and replace worn parts

Shortage of water

Strainer at water inlet fitting clogged

Remove strainer and clean

Float reservoir water nozzle clogged-up

nozzle

Remove float valve and clean

MDT2

May 2002

Page 20