Capswitcher, Title, Vertical interrupter style capacitor switcher – Southern States 38 kV-170 kV CapSwitcher User Manual

Page 3: Product specification guide

Advertising
background image

Title:

Southern States 38 kV–170 kV

CapSwitcher

®

Vertical Interrupter Style Capacitor Switcher

Product Specification

Guide

Page 3 of 10

Publication No.: PSG-807-031109

Rated Maximum
Voltage

38 kV

48.3 kV

72.5 kV

123 kV

145 kV

170 kV

Rated Power
Frequency Withstand
Voltage

80 kV

105 kV

160 kV

260 kV

310 kV

365 kV

Rated Lightning
Impulse Withstand
Voltage (BIL)

200 kV

250 kV

350 kV

550 kV

650 kV

750 kV

Rated Power
Frequency

50/60 Hz

Rated Continuous
Current

600 A

650 A

Peak Withstand
Current

104 kA

164 kA

Short-Time
Symmetrical
Withstand

40 kA RMS 1 sec

40 kA RMS 1 sec,

63 kA RMS 18 cycles

Rated Short Circuit
Interrupting Current

25 kA

40 kA

Number of Full Fault
Operations

30

10 at 40 kA, 15 at 31.5 kA, 30 at 20 kA

Interrupting Speed

5 cycles

3 cycles

Fault Closing

10 time 40 kA, 15 time 31.5 kA,

30 time 20 kA

2 time 63 kA, 10 time 40 kA,

15 time 31.5 kA, 30 time 20 kA

Rated Duty Cycle

CO – 5 min – CO – 5 min – CO

(Note: The 5 minutes is to allow the substation capacitor bank to discharge.)

CAPACITOR SWITCHING RATINGS

Rated Capacitive
Switching Current

600 A

650 A

Back-To-Back
Capacitor Bank
Breaking Current

600 A

650 A

Rated High-Frequency
Transient-Making
Current / Transient
Inrush Frequency

18 kA peak / 4630 Hz

20 kA peak / 4600 Hz

Resistor Value

See Table in 3.03.01

Pre-insertion time 5-15 ms

3.02.02 Additional

The capacitor switcher shall have an endurance life of 10,000
operations.


Advertising