Super Systems AC20 Quick Start User Manual

Ac20 quick start instructions, Keyboard description

Advertising
background image

Super Systems Inc.

1

1 (800)-666-4330

Cincinnati, OH 45241

Fax: (513) 772-0060

//Ssio1/main/.ssimanuals/ac20qs

www.supersystems.com

Keyboard Description:

MENU Is used to select a parameter group

FUNC: when the instrument is in Normal Display Mode changes the indication on

the lower display (default display is % of control output)

MAN: When the instrument is in Normal Display Mode, pushing MAN for more

than one second enables or disables the manual function

Press

⇑⇑

Key during parameter modification to increase the value of the selected

parameter.

Press

⇑⇑

Key during MANUAL Mode to increase the output value

Press

⇓⇓

Key During parameter modification to decrease the value of the

selected parameter.

Press

⇓⇓

Key during MANUAL Mode to decrease the output value

Press

TST+MAN Hold TST and then press MAN button to start the Burnoff

function.

*

Press

TST+FUNC Hold TST, then press

FUNC Button to start the Probetest

function.

Test + MENU Are used to start the lamp test function (the command is accepted

when push-buttons are kept depressed for more that 5 seconds and the
instrument is in normal display mode)

Press

TEST + FUNC during parameter modification to increase/decrease the

value under modification to higher rate.

Press

TEST+MAN

during parameter modification to jump to the max or min

programmable value.

Two conditions apply: First, the burnoff function must be configured and second, it must be at

least 10 minutes from the last burnoff, for the test to st

art