To Verify that your change was accepted you may view the H

2

F by pressing the FUNC

button until you reach H

2

F in the lower Display.

To Change to Burnoff Timers:

When the device is in AUTO Mode and in Normal Display Mode

q

Press the MENU button – (Gr. 1 will be displayed in Yellow)

q

Press the MENU button until you reach Gr. 8 displayed in Yellow

q

Pressing the FUNC button to scroll through parameters (refer to Operators Manual
for description of parameters)

q

After achieving the desired set points, you must press the FUNC button once again
after every change for it to be accepted.

q

The instrument will time out for 30 seconds and return to “Normal Display Mode or
you may press the MENU button several times until you return to Normal Display
Mode

To Perform A Probe Burn-off

q

Press the TST button and Hold then press the MAN button
The burnoff will begin and after it is completed, it will return to Normal Display Mode

To Perform A Probe Test

q

Press the TST button and Hold then press the FUNC button

q

The ProbeTest will begin and after it is completed, it will return to Normal Display
Mode

q

To display the results of the test, press the FUNC button until SEC (Sensor response
Time), and K (Probe resistance).