3 analog output wiring – Tecfluid CU Series User Manual

Page 8

Advertising
background image

8

2

The relay outputs are SPDT relays with potential free contacts (see characteristics in
page 40).
The state of the relay contacts corresponds to the relay at rest

.

The relay contacts are not protected in any way, and therefore they must be installed
externally

as required in the application

, taking into account the limitations of the

characteristics of such contacts. In the case of having inductive loads, and to extend the
working life of the contacts of the relays, it is recommended to use overvoltage protection
(VDR for AC and diodes for DC loads). In all cases a fuse or some type of short circuit
protection against short circuits,

should always be provided

according to the needs of the

intended load.

2.1.3 Analog

output

wiring

Terminal

+

mA

(positive)

-

mA

(negative)

INSTALLATION OF THE ELECTRONIC CONVERTER

Passive mode: pins 2&3
Active mode: pins 1&2