2.3.2 TWO PUMP CASCADE SYSTEM

In this configuration

will run when the tank temperature

is below the

set point TT, and Pump

will run (Pump

will switch off) when

rises

above TT.

1

Insert a link between “L” terminal of the PUMP relay and the common
terminal “C” of the AUX relay, (see cascade diagram).

2

Connect

and

(see cascade diagram)

3

Connect the mains supply to the terminals marked MAINS

4

Connect the earth to the pump.

Replace the “top” section of the control unit, and then fasten using the two
side fixing screws. The unit is now ready to be powered up.

When

< TC:

= OFF;

= OFF

When

> TC

: If

< TT::

= ON;

= OFF

and

-

>

If

> TT::

= OFF;

= ON