Interface specifications

Power RV-07, 17 pcs TR-36, PS-20 HV

Power supply

110 – 250 VDC +10 / –10%
115 – 230 VAC +15 / –10%

Power consumption

500/240 mA, 50 W

Rated frequency

DC / 48 – 62 Hz

Fuse, F1

4 AS 5x 20 mm

Isolation to

All other ports 3 kV

rms

50 Hz 1 min

Connection

Detachable screw terminal

Shielded cable

Not required

* Direction relative this unit

Power RV-07, 17 pcs TR-36, ext 24 – 48 VDC

Power supply

24 – 48 VDC

Power consumption

34 W

Rated frequency

DC

Isolation to

All other ports 1.5 kV

rms

50 Hz 1 min

Connection

Detachable screw terminal**

Shielded cable

Not required

* Direction relative this unit
** Maximum wire length to external power supply < 10 m.

Public Switched Telephone Network (PSTN)

Electrical specification

Public Switched Telephone Network

Data rate

300 bit/s to 33.6 kbit/s

Protocol

B103, B212, V21, V22, V22B, V23C,V23HDX, V32, V32B, V34

Protection

Installation Fault Tolerant (up to ±60 V)

Isolation to

Power port

3 kV

rms

50 Hz 1 min

Leased line

2 kV

rms

50 Hz 1 min

RS-232

2 kV

rms

50 Hz 1 min

RS-485

2 kV

rms

50 Hz 1 min

Connection

Detachable screw terminal

Shielded cable

Not required