Self Cleaning Continuous Filter Chapter 3: Installation

24

Installing Pressure Gauge

1. Install the differential pressure gauge according to the detailed instruction sheet

packed in the box with your gauge.

2. Mount the gauge in a location that is free from excessive vibration and where the

temperature does not exceed 140°F. Avoid direct sunlight.

3. For permanent installations, it is recommended that ¼” O.D. copper tubing be used

with regular compression fittings. An in-line paper filter will prevent dust from
getting into the gauge line. If this is not used, it is recommended that a loop be
placed in the high pressure gauge line that leads from the dirty air housing so that
dust does not enter the gauge.

4. Adjust the differential pressure gauge to indicate zero.

Figure 13: Connecting Differential Pressure Gauge

Note: Drawing may not depict current unit. Contact manufacturer’s

engineering department for current drawings.