To avoid electric shock, never open the chassis of the RPS1600-A
while it is in operation; try not to open the RPS1600-A even if it is
not electrified.

Unplug the power cable before cleaning the RPS1600-A.

Keep the equipment room clean. The limits on the concentrations of
dust and harmful gases in the equipment room are shown in

Table

5

and

Table 6

.

Table 5 Limit on dust concentration

Mechanical active material Limit

(particles/m

3

)

Dust particles

≤ 3 x 10

4

(No visible dust on desk

in three days)

Note: Dust particle diameter ≥ 5 μm

Table 6 Limits on harmful gas concentration

Gas Limit

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01

Installing the RPS1600-A

The RPS1600-A can be installed either in a 19-inch standard rack or on
a workbench.