12  Additional Functions

SMA America, LLC

104

SI4548-6048-US-BE-en-20

Operating Manual

12.2 Sleep Mode

Using the parameter "250.10 SleepEna" set to "Enable" allows the sleep mode to be activated in
single-phase utility grids which the master uses to switch off the slaves when the power value allows
this.

12.3 Time-Controlled Operation

The Sunny Island can be operated in a time-controlled manner using a timer function (like a clock
timer), supplying power at a planned point in time.
This function must be activated by using the parameter "510.02 InvTmOpEna". Using the parameter
"510.03 InvTmOpStrDt", you can specify the start date, and using the parameter
"510.04 InvTmOpStrTm", you specify the start time. With the parameter "510.05 InvTmOpRnDur",
you set the running time and with the parameter "510.06 InvTmOpCyc", you determine whether this
function will be carried out once, every day or weekly, at or from the specified start time (date and
time).

12.4 Overload and Short-Circuit Behavior

The Sunny Island can be temporarily operated under overload conditions. and is able to supply
short-circuit current.
In the event of overload, the Sunny Island 4548-US supplies a power of 5,300 W for 30 minutes at
77°F (25°C) and the Sunny Island 6048-US a power of 7,000 W. Both Sunny Island inverters can
deliver a power of 7,200 W for 5 minutes at 77°F (25°C). The available power can even reach
8,400 W for 1 minute at 77°F (25°C).
In the event of a short circuit, the Sunny Island provides a maximum current of 180 A (for 60 ms). This
is sufficient to trip commercial 20 A circuit breakers.

12.5 Mixed Operation with Sunny Island Inverters of Different

Power

The Sunny Island inverters 4548-US, 6048-US and 5048U can be operated in an off-grid system
together.
Each Sunny Island makes its contribution to cover the current power requirements of the loads. This
contribution is made up of the ratio of the nominal power of each Sunny Island to the overall power
of all Sunny Island inverters.
If an SI 5048U is installed in an off-grid system configure the SI 5048U as slave or equip with the
latest firmware (see www.SMA-America.com).

Sleep mode
The "Sleep Mode" works exclusively in stand-alone mode. The values for connection and
disconnection of the Sunny Island are already set at the factory (optimized in terms of
efficiency).