15 relays – SMA SI 4548-US User Manual

Page 139

Advertising
background image

SMA America, LLC

15  Relays

Operating Manual

SI4548-6048-US-BE-en-20

139

15 Relays

The Sunny Island offers you several options for the control of internal and external processes. Two
multi-function relays are integrated into the device to which you can assign functions using the
parameters "241.01 Rly1Op" and "241.02 Rly2Op" (see Section 6.4.6 "Multifunction Relay 1 and
2", page 58).
The different settings have the following meanings:

Function/
Setting

Meaning

Function description

Off

Off

Relay remains permanently switched off
(deactivated).

On

On

Relay remains permanently switched on (e.g. relay
function test during commissioning).

AutoGn

Automatic generator request The generator is automatically activated due to set

criteria (see Section 14.1.5 "Automatic Generator
Operation", page 122).

AutoLodExt

Automatic load shedding
dependent on an external
source

Automatic connection / disconnection of loads.
Connection occurs if the device is connected to an
external source (e.g. generator), or if the Lod1Soc
limits are exceeded (see Section 12.1 "Load
Shedding", page 102).

AutoLodSoc1 Auto LoadShedding Soc1

Automatic connection / disconnection of loads.
Connection only if Lod1Soc limits are exceeded
(see Section 12.1 "Load Shedding", page 102).

AutoLodSoc2 Auto LoadShedding Soc2

Automatic load disconnection. Connection only if
Lod2Soc limits are exceeded (see Section 12.1
"Load Shedding", page 102).

Tm1

Timer 1 (time-controlled
switching of relay 1)

Programmable timer (once, daily, weekly) with
duty cycle.

Tm2

Timer 2 (time-controlled
switching of relay 2)

Programmable timer (once, daily, weekly) with
duty cycle.

AptPhs

Absorption phase is active

Relay switching when battery charge is in
absorption phase.

ExtPwrDer

External power reduction

The Sunny Island controls additional loads in order
to put excess energy to practical use. When
excessive energy can be used, the multifunction
relay is activated.

GnRn

Generator active

Relay switching when generator is in operation
and connected.

Advertising
This manual is related to the following products: