Serial Interface Protocol

213

6.2.3.3. Response Message Format Example

CONTROL ON command

Example of response message to CONTROL_ON command to axis 0

in Immediate mode with message identification of 0x7F.
Master Message Format:

N A

M

I

D

1 I

D

2 C1 C2 V1 V2 P1 P2 S1 S2 CR

N 0 A 7 F 4 5 0 0 0 1 3 1 CR

Response Message Format in case of no fault:

N A

M

I

D

1 I

D

2 F1 F2 SW1 SW2 SW3 SW4

N

0

0

0 0 0 0 0 4 3 7

S1 S2 CR

C 5 CR

Where:

A = 0

Axis number 0

m = 0

Response type is acknowledge without Fault

ID1 = 0; Id2 = 0

No fault, so message identification is 0x00

F1 = 0; F2 = 0

No fault, so fault code is 0x00

SW1=0; SW2=4;
SW3=3; SW4=7

Shows FSP Amplifier status. No emergency,
no fault, control on and in position (See

Chapter 10, List of Status Word Bits)

S1=C; S2=5

0x100–(00+00+00+0x04+0x37)= 0xC5