Dvvk-4re vent kit installation instructions – Empire Comfort Systems DVX36DP31 User Manual

Page 26

Advertising
background image

25613-0-0309

Page 26

CAUTION: Sharp edges, use protective gloves when

installing.
Tools Needed for Installation:

Sheet metal snips

5/16” nut driver

Phillips head screwdriver - #2

High temperature sealant or furnace cement rated for continuous

use at 1,000

o

F minimum

Measuring tape

Parts Verification

See parts list on page 28 to verify components included in this vent

kit prior to installation.

NOTE: If installing onto wood, lap, or vinyl siding, the vinyl siding

kit should be used (sold separately, part number DV-822).
The vinyl siding vent kit, DV-822, is available from Empire Comfort

Systems, Inc. The depth is 3” (76 mm), which enables the vent cap

to be extended away from vinyl siding or projections. The wall depth

plus the additional 3” (76 mm) depth of the vinyl siding vent cap

extension should not exceed a total depth of 13 3/4” (349 mm).
If wall depth exceeds 13 3/4” (349 mm), extend system using

6 5/8” (168 mm) x 4” (102 mm) rigid venting (See Fireplace In-

structions for approved lengths) See Figure 38.
Installing Wall Thimble/Firestop Assembly
1. Fix fireplace to permanent location. If using rigid venting sys-

tem, install up to the location where it will exit the building.

2. Cut hole in wall for wall thimble/firestop assembly into your

combustible wall. See Figure 37. Note: On brick or block

exterior wall a 7” (178 mm) diameter hole needs to be cut.

Measure the total wall thickness to determine whether or not

the extension thimble is to be used. If the combustible wall

depth is over 5 3/8” (137 mm), then the extension thimble

should be used. See Figure 37.

3. Install the wall thimble assembly through the framed

opening so the firestop plate is on the interior wall. See

Figure 37. Telescope section should extend all the way through

the exterior wall. Attach with (4) 10 x 1” screws.

4. When placing the vent cap on an exterior wall covered with

combustibles such as wood, lap, or vinyl siding, install the

vinyl siding kit to the exterior wall sheathing.

Figure 37

Figure 38

Cutting Vent Tubes
This is the most important part of the installation.
With the

fireplace (and the rigid venting system if used) fixed to its permanent

location, the 6 5/8” (168 mm) diameter air inlet tube and the 4”

(102 mm) diameter flue outlet tube are to be marked and cut using

the following procedure.
5. Attach the inlet tube to the outside mounting plate. Align

tinnerman clips on the tabs of the air inlet tube to the holes on

outside mounting plate, and fix with (2) #10 x 1/2” screws.

6. With the vinyl siding kit installed to wall (if necessary), insert

the 6 5/8” (168 mm) diameter tube with outside mounting plate

attached through hole in wall. Connect to collar on fireplace or

rigid vent system. Measure between wall or vent cap extension

and outside mounting plate (Figures 39 and 40).

11”

9”

NOTE: SPACING FLANGE

INSTALLED TO TOPSIDE

INTERIOR WALL

EXTENSION
THIMBLE

DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS

X

X = 13 3/4” MAX

TOTAL WALL THICKNESS

(SUBTRACT 3” IF USING THE

DV822 VINYL SIDING KIT)

½” AIR SPACE
CLEARANCE