Yaskawa G5 PID for Trim Control User Manual

Page 5

Advertising
background image

Date: 07/01/04, Rev: 04-07

Page 5 of 12

TM.G5SW.012



b5-10: PID Position High


b5-11:
PID Position Low


b5-12: PID Hysteresis


H2-01: Multi-function Output (Terminals 9-10)
H2-02:
Multi-function Output (Terminals 25-27)
H2-03: Multi-function Output (Terminals 26-27)


Parameters b5-10, b5-11, and b5-12 are used in conjunction with one or two multi-function outputs. With these a Multi-
function Output can be activated when the feedback signal goes above a certain level (b5-10), or drops below a certain
level (b5-11). Parameter b5-12 determines at what point the Multi-function Output will de-energize.

Factory Setting: 10.00
Range: -10.00 - +10.00V

Factory Setting: 0.00
Range: -10.00 - +10.00V

Factory Setting: 0.10
Range: 0.00 - 1.00V

Data 40: High Position

or

Data 41: Low Position

EXAMPLE OF POSITION HIGH AND POSITION LOW OUTPUTS