I.3 electrical installation safety – Yaskawa AC Drive Z1000 HVAC User Manual

Page 20

Advertising
background image

Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb. in.)

2A0024

R/L1, S/L2, T/L3

8

14 to 8

M4

1.6 to 1.8

(14 to 16)

U/T1, V/T2, W/T3

8

-M, +M

M5

2.7 to 3.0

(24 to 27)

2A0031

<1>

R/L1, S/L2, T/L3

8

14 to 8

M4

1.6 to 1.8

(14 to 16)

U/T1, V/T2, W/T3

8

-M, +M

M5

2.7 to 3.0

(24 to 27)

2A0046

<1>

R/L1, S/L2, T/L3

6

10 to 4

M5

2.7 to 3.0

(24 to 27)

U/T1, V/T2, W/T3

6

-M, +M

2A0059

<1>

R/L1, S/L2, T/L3

4

10 to 4

M5

2.7 to 3.0

(24 to 27)

U/T1, V/T2, W/T3

4

-M, +M

2A0075

<1>

R/L1, S/L2, T/L3

3

8 to 2/0

M8

5.4 to 6.0

(48 to 53)

U/T1, V/T2, W/T3

3

-M, +M

2A0088

<1>

R/L1, S/L2, T/L3

2

8 to 2/0

M8

5.4 to 6.0

(48 to 53)

U/T1, V/T2, W/T3

2

-M, +M

2A0114

<1>

R/L1, S/L2, T/L3

1/0

8 to 2/0

M8

5.4 to 6.0

(48 to 53)

U/T1, V/T2, W/T3

1/0

-M, +M

2A0143

<1>

R/L1, S/L2, T/L3

3 × 2

1/0 to 3/0

M8

13.5 to 15.0

(120 to 133)

U/T1, V/T2, W/T3

3 × 2

-M, +M

2A0169

<1>

R/L1, S/L2, T/L3

2 × 2

1/0 to 3/0

M8

13.5 to 15.0

(120 to 133)

U/T1, V/T2, W/T3

2 × 2

-M, +M

2A0211

<1>

R/L1, S/L2, T/L3

1/0 × 2

1/0 to 3/0

M8

13.5 to 15.0

(120 to 133)

U/T1, V/T2, W/T3

1/0 × 2

-M, +M

2A0273

<1>

R/L1, S/L2, T/L3

2/0 × 2

1/0 to 4/0

M10

27.0 to 30.0

(239 to 266)

U/T1, V/T2, W/T3

2/0 × 2

-M, +M

M8

13.5 to 15.0

(120 to 133)

i.3 Electrical Installation Safety

20

YASKAWA ELECTRIC TOEP YAIZ1U 01A YASKAWA AC Drive – Z1000 Safety Precautions

Advertising