Control circuit output terminals, Table i.9 – Yaskawa AC Drive Z1000 HVAC User Manual

Page 29

Advertising
background image

Table i.9 Control Circuit Input Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Multi-Function

Digital Inputs

S1

Multi-function input 1

(Closed: Forward run, Open: Stop)

• Photocoupler
• 24 Vdc, 8 mA
• Set the wire jumper to select between sinking, sourcing mode, and the

power supply.

Refer to Sinking/Sourcing Mode Switch for Digital

Inputs on page 36

.

S2

Multi-function input 2

(Closed: Reverse run, Open: Stop)

S3

Multi-function input 3

(External fault, N.O.)

S4

Multi-function input 4

(Fault reset)

S5

Multi-function input 5

(Multi-step speed reference 1)

S6

Multi-function input 6

(Multi-step speed reference 2)

S7

Multi-function input 7

(Jog reference)

SC

Multi-function input common

Multi-function input common

SP

Digital input power supply +24 Vdc

24 Vdc power supply for digital inputs, 150 mA max

NOTICE: Do not jumper or short terminals SP and SN. Failure to

comply will damage the drive.

SN

Digital input power supply 0 V

Frequency

Reference

Inputs

+V

Power supply for analog inputs

10.5 Vdc (max allowable current 20 mA)

A1

Multi-function analog input 1

(Frequency reference bias)

• 0 to 10 Vdc/100% (input impedance: 20 kΩ)
• 4 to 20 mA/100%, 0 to 20 mA/100% (input impedance: 250 Ω)
• Voltage or current input must be selected by Jumper S1 and H3-01.

A2

Multi-function analog input 2

(Frequency reference bias)

• 0 to 10 Vdc/100% (input impedance: 20 kΩ)
• 4 to 20 mA/100%, 0 to 20 mA/100% (input impedance: 250 Ω)
• Voltage or current input must be selected by Jumper S1 and H3-09.

AC

Frequency reference common

0 V

FE

Ground for shielded lines and option cards

u

Control Circuit Output Terminals

Table i.10

lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.

Table i.10 Control Circuit Output Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Fault Relay

Output

MA

N.O.

30 Vdc, 10 mA to 2 A; 250 Vac, 10 mA to 2 A

Minimum load: 5 Vdc, 10 mA

MB

N.C. output

MC

Fault output common

Multi-Function
Digital Output

<1>

M1

Multi-function digital output (During run)

30 Vdc, 10 mA to 2 A; 250 Vac, 10 mA to 2 A

Minimum load: 5 Vdc, 10 mA

M2
M3

Multi-function digital output (Zero speed)

M4
M5

Multi-function digital output (Speed Agree 1)

M6

Monitor Output

FM

Analog monitor output 1 (Output frequency)

0 to 10 V / 0 to 100%

4 to 20 mA / 0 to 100%

Voltage or current output must be selected by Jumper S5 and H4-07

for FM and H4-08 for AM.

AM

Analog monitor output 2 (Output current)

AC

Monitor common

0 V

External Power

Supply

+P

External Power Supply

24 V (Max. 150 mA)

<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life. Switching

life is estimated at 100,000 times (assumes 2 A, resistive load).

Connect a suppression diode as shown in

Figure i.15

when driving a reactive load such as a relay coil. Ensure the diode rating

is greater than the circuit voltage.

i.3 Electrical Installation Safety

YASKAWA ELECTRIC TOEP YAIZ1U 01A YASKAWA AC Drive – Z1000 Safety Precautions

29

Advertising