Altitude derating, Dimensions, weight, heat loss, Dimensions, weight, heat loss notice – Yaskawa AC Drive Z1000 HVAC User Manual

Page 46

Advertising
background image

External Heatsink Installation

Drive operation between -10 °C and +40 °C (14 and 104 °F) allows 100% continuous current without derating. Operation

between 40 °C and 50 °C (104 and 122 °F) requires output current derating.

40

°C

100%

60%

-10

°C

0%

50

°C

80%

IP20/NEMA Type 1

IP00/Open-Type

External Heatsink

Figure i.27 Ambient Temperature and Installation Method Derating

u

Altitude Derating

The drive standard ratings are valid for installation altitudes up to 1000 m. For installations from 1000 m to 3000 m, the drive

rated output current must be derated for 0.2% per 100 m.

u

Dimensions, Weight, Heat Loss

NOTICE

Refer to the Mechanical Installation Chapter and the Specifications Chapter of the Z1000 User Manual
TOEPC71061645
which can be found on the CD-ROM packaged with the product.

i.6 European Standards