Carrier Frequency Selection: C6-02

Fixed Carrier Frequencies

The carrier frequency can be set using parameter C6-02 as shown in table below.

Parameter

Name

Description

Setting Range

Default

C6-02

Carrier

Frequency

Selection

1 : 2.0 kHz

2 : 5.0 kHz

3 : 8.0 kHz

4 : 10.0 kHz

5 : 12.5 kHz

6 : 15.0 kHz

7: Swing PWM 1

8: Swing PWM 2

9: Swing PWM 3

A: Swing PWM 4
B: Leakage Current Rejection PWM

<1>

F : User defined (C6-03 to C6-05)

1 to B, F

Determined by

A1-02 and

o2-04.

Reset when

C6-01 is

changed.

<1>

Available in drive software versions PRG: 1020 and later. Setting B uses a PWM pattern that reduces the amount
of leakage current detected over long wiring distances. This can help reduce alarm detection and problems with
the current monitor that result from leakage current over long wiring distances. This is the same as setting the
carrier frequency to 2 kHz.

Note:

1. Swing PWM uses 2.0 kHz carrier frequency as a base. Applying special PWM patterns minimizes

the audible noise of the motor.

2. The upper limit for the carrier frequency is determined by drive capacity.

u

Drive Input Voltage Setting: E1-01

Set E1-01 according to the power supply voltage. This setting serves as a base value for certain

drive protective functions.

NOTICE: Set drive input voltage (not motor voltage) in parameter E1-01 for proper function of the protective

features of the drive. Failure to comply could result in improper drive operation. Set parameter E1-01 to match

the input voltage of the drive.

Parameter

Name

Description

Setting Range

Default

E1-01

Input

Voltage

Setting

Set to the nominal voltage of the incoming line. Sets

the maximum and base voltage used by preset V/f

patterns (E1-03), and adjusts the levels of drive

protective features (e.g., overvoltage, braking resistor

level, stall prevention, etc.).

200 V Class: 155 to 255

400 V Class: 310 to 510

230 V

<1>

<1>

The default value shown here is for 200 V class drives. Double the value for 400 V class drives.

4.6 Basic Drive Setup Adjustments

112