Application Selection

Several Application Presets are available to facilitate drive setup for commonly used

applications. Selecting one of these Application Presets automatically sets the required

parameters to the Application Preset default values and selects I/Os. In addition, the

parameters most likely to be changed are assigned to the list of User Parameters, A2-01

through A2-16. These can be accessed in the Setup Mode and provide quicker application

adjustment by eliminating the need to scroll through multiple menus.
The following presets can be selected:

Note:

1. Do not set any value outside the allowable range for A1-06. Setting an out-of-range value will cause

“APPL” to flash on the display in the Setup group and disable the up and down arrow keys on the

digital operator. To fix this error, press the ESC key to return to the Setup group and then it will then

be possible to switch to another mode using the up and down arrow keys.

2. A1-06 setting can only be changed by initializing the drive by first setting A1-03 to 2220. Setting

A1-06 to a value that is out of range will not adversely affect drive operation. When the drive should

not be initialized because initialization will cause other problems, then A1-06 does not need to be

changed.

WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting

parameter A1-06 may change the I/O terminal function automatically from the default setting. Failure to comply

may result in death or serious injury.

No.

Parameter Name

Setting Range

Default

A1-06

Application Preset

0: Disabled

1: Water supply pump

2: Conveyor

3: Exhaust fan

4: HVAC

5: Compressor

<1>

8: Conveyor 2

<2>

0

<1>

Application Preset settings 6 and 7 are only available in drive software versions PRG: 5010, PRG: 1010, and
PRG: 1011. To determine the drive software version, refer to the PRG: field on the drive nameplate or drive
parameter U1-25.

<2>

Available in drive software versions PRG: 1020 and later.

u

Setting 1: Water Supply Pump Application

Table 4.3 Water Supply Pump Parameter Settings

No.

Name

Default Setting

A1-02

Control Method Selection

0: V/f Control

b1-04

Reverse Operation Selection

1: Reverse Prohibited

C1-01

Acceleration Time 1

1.0 s

C1-02

Deceleration Time 1

1.0 s

4.5 Application Selection

96