7 Troubleshooting

7 Troubleshooting

Problems with the option interface may trigger an operator error.

Refer to the J1000 Technical Manual for all other errors.

Fault

LED Operator

Display

Minor Fault Name

CE

MEMOBUS/Modbus Communication
Error

Cause

Possible solutions

Data not received
within the CE
detection time
limit set in
parameter H5-09.
This is possibly
due to noise or a
improperly
connected
communication
cable.

⇒Check for improper wiring or loose
cables.

⇒Make sure the unit is properly grounded.

⇒Reconnect leads running to the main
circuit in the drive.

⇒Make sure the DIP switch for terminal
resistance is set appropriately.