7 Troubleshooting

YASKAWA ELECTRIC

TOBPC73060033A RS-485 Interface Technical Manual

25

oPE05

Run Command Selection Error
The Run command selection parameter b1-
02 is set to 3 but no option unit is installed.

Cause

Possible solutions

Frequency
reference is
assigned to an
option (b1-01 = 2)
that is not
connected to the
drive.

⇒Make sure that parameters b1-01 and b1-
02 are set properly.

⇒Reconnect the option unit to the drive.

The Run command
is assigned to an
option (b1-02 = 2)
that is not
connected to the
drive.

LED Operator

Display

Minor Fault Name