Sending/Receiving Data

Data that can be sent and received are run/stop commands, frequency reference, fault reset, Drive
status, and setting and reading of parameters.

n02

: Operation Method Selection

Factory setting:

0

Range: 0 to 2

Parameter

n02

selects where the run/stop commands (sequence) will come from. To be able to

provide a run command over the Modbus serial communications link, set this to a data of “2.”

n03

: Reference Selection

Factory setting:

0

Range: 0 to 6

Parameter

n03

selects where the frequency reference will come from. To be able to provide a

frequency reference over the Modbus serial communications link, set this to a data of “6.”

n36

thru

n39

: Multi-function Inputs

Data

18

: Serial communication/

(Term. S2-S5)

Digital Operator

Selects operation by serial communication or by external terminal. If the status of this command input
is changed while the Drive is running, the selection is ignored until the next time the Drive is stopped.

Open

: Run according to the setting of Operation Method Selection (

n02

) and

Reference Selection (

n03

).

Closed

: Run by frequency reference and run command from serial

communication.

EXAMPLE:

n02

setting is " 1 ", and

n03

setting is " 2 ".

n39

= 18.

TERMINAL S5 Open:

Frequency reference from control circuit terminal FR
and run command from control circuit terminals S1, S2.

TERMINAL S5 Closed: Frequency reference and run command from serial

communication.

5.14 MODBUS CONTROL