6.1 Common Settings

6 - 15

D

The following table shows which frequency is selected by each possible combination of multi-step

speed and JOG reference settings.

Terminal 13

Terminal 14

Terminal 15

Terminal 16

Multi-step speed

reference 1

Multi-step speed

reference 2

Multi-step speed

reference 3

JOG reference

Selected frequency

OFF

OFF

OFF

OFF

Reference 1: d1-01 (master

speed frequency)

ON

OFF

OFF

OFF

Reference 2: d1-02 (auxilia-

ry speed frequency)

OFF

ON

OFF

OFF

Reference 3: d1-03

ON

ON

OFF

OFF

Reference 4: d1-04

OFF

OFF

ON

OFF

Reference 5: d1-05

ON

OFF

ON

OFF

Reference 6: d1-06

OFF

ON

ON

OFF

Reference 7: d1-07

ON

ON

ON

OFF

Reference 8: d1-08

--

--

--

ON

Jog frequency: d1-09

Selecting 1-step and 2-step Frequency References

D

To use the master frequency (analog terminal 36 or 39), set b1-01 to 1.

D

To use frequency reference 1 (d1-01), set b1-01 to 0.

D

To use the auxiliary frequency reference (analog terminal 42), use the factory setting.

D

To use frequency reference 2 (d1-02), set H3-05 to 1F.

Frequency

reference

Reference 1
Master speed

Reference 2
Auxiliary speed

Reference 3

Reference 4

Reference 5

Reference 6

Reference 7

Reference 8

RUN/STOP

Multi-step speed reference 1

Multi-step speed reference 2

Multi-step speed reference 3

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

JOG reference

JOG frequency

Fig 6.10

Timing Chart for Multi-step Speed and JOG References