7.5 Common Functions

7 - 87

Minimum Baseblock Time: L2-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L2-03

Min. baseblock time

x

0.0 to 25.5

s

10.0

B

B

B

B

D

The factory setting depends on the Inverter capacity. The factory setting shown in the table is for a 400-V

class, 200 kW Inverter. (See page 8 - 42.)

D

This setting is used with the speed search and DC injection braking functions.

D

Set the time required for the leakage voltage to dissipate. Increase the setting if an overcurrent (OC)

occurs when the speed search or DC injection braking function starts.

D

This setting is valid for speed searches performed after a momentary power loss and regular speed

searches.

Voltage Recovery Time: L2-04

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L2-04

Voltage recovery time

x

0.0 to 5.0

s

0.3

A

A

A

A

D

Set the time allowed for the normal voltage to be restored after completion of the speed search.

For a 400-V class Inverter, this is the time in seconds for voltage to be restored from 0 VAC to 400 VAC.

For a 575-V class Inverter, this is the time in seconds for voltage to be restored from 0 VAC to 575 VAC.

D

This setting is valid for speed searches after a momentary power loss, regular speed searches, the voltage

changes with energy-saving control, and the voltage changes with baseblock clearing.

Undervoltage Detection Level: L2-05

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L2-05

Undervoltage detec-

tion level

x

300 to 420

(430 to 600) VDC

380

(570)

A

A

A

A

D

The values in parentheses are for 575-V class Inverters. (See page 8 - 43.)

D

Normally it isn’t necessary to change this setting.

D

Use this constant when you want to add an AC reactor and lower the main circuit undervoltage detection

level. Be sure to set a main circuit DC voltage value (V) that will detect a main circuit undervoltage.

KEB Deceleration Rate: L2-06

Although L2-06 is displayed on the Digital Operator, it cannot be set.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L2-06

KEB deceleration rate

x

0.0 to 100.0

0.1

0.0

A

A

A

A

D

The KEB function restores the operating conditions for momentary power loss by applying a frequency

deceleration to create inertia energy when a power loss occurs, and thus avoid the power loss.

D

This function is normally used with film lines and other applications where multiple Inverters are con-

nected to the main DC line. Synchronous deceleration for power loss prevents the line from stopping

as the result of speed fluctuations.

D

The KEB operation is performed using a KEB command (setting of 65 or 66) for a multi-function input.

D

Applicable Capacities: 400-V class Inverters: 0.4 to 18.5 kW.

Operation

D

L2-06 = 0

The motor is automatically accelerated based on the emergency stop time (C1-09) so that the DC main-

line voltage does not go below the UV level. The momentary power loss ridethru time (L2-02) is not

used.

7

IMPORTANT