Power source installation, Circuit breaker diagnostic system – Irritrol MC-E User Manual

Page 7

Advertising
background image



Power Source Installation

WARNING: All electrical components and installation practices must meet applicable national and local electrical

codes including installation by a qualified personnel. These codes may require an external junction box mounted on the

cabinet and a circuit breaker in the main wiring having a contact separation of at least 0.120” in the line and neutral poles.
The 120 VAC power source must be turned OFF prior to servicing. The power cable used for connection to the controller

must have an insulation rating of 221° F minimum.

Step 1 – For power source connection, install a 1/2” electrical

conduit from the 120 VAC power source to the MC-E

controller cabinet.

Step 2 – Install an electrical junction box at the transformer to

allow access for future servicing.

Step 3 – Confirm that power has been disconnected at the power

source using a volt meter or voltage detector.

Step 4 – Route 14-AWG insulated solid copper wires for Power

(Black), Neutral (White) and Equipment Ground (Green)

through the conduit and into the junction box.

Step 5 – Strip back 3/8” of insulation from each wire. Using wire

connectors, connect the wires with similar colors together

(Black with Black, White with White, etc.).

Step 6 – Tuck the wires inside the junction box and replace the

cover.

Step 7 – Apply power to the controller.

Circuit Breaker Diagnostic System

The controller’s system for managing an electrical short circuit is designed to isolate the station with the problem and

continue to water operable stations. The sequence the controller follows is listed below.
1. The controller reaches a station with a short circuit.
2. The controller shuts off the problem station and skips to the next station in the same program and continues operation.
3. The controller displays “Fuse Alarm on __” and the problem station’s number as well as the other station in operation.
4. In between programs, when the controller is idle, it will display the Fuse Alarm station alternating with the display of

Day/Date/Time.

5. The next time the controller is supposed to run the station, it will try again. If the cause of the short has been repaired,

the Fuse Alarm will disappear from the display and the station will run normally. You can also use the CLEAR button

to clear the Fuse Alarm from the display. This does not fix the shorted circuit, but only clears its display.

The controller has fractions of a second to detect and shutoff the problem station before the short circuit causes

damage. On occasion, with multiple programs and stations running, the controller shuts off and displays two stations as

having shorts. You can test each station in MANUAL mode or with STATION TEST to find the shorted one.

VALVE

COMMON

VALVE

COMMON

VALVE

COMMON

MASTER

VALVE

YEL RED

VALVE

COMMON

GND

1

3

5

7

9

11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41

2

4

6

8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42

1

3

5

7

9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47

2

4

6

8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48

Power Wire = Black
Neutral Wire = White
Equipment Ground = Green