Proportional-Reset Controllers

1.

The air supply should be connected to Bellofram

Mark 50 filter regulator.

2.

Connect the control pressure line and open the

lock shield needle valve.

3.

Ensure all piping and connections are free from

leaks.

4.

Set pressure to the desired control point.

5.

Proportional band should be set at 100% of

bandwidth.

6.

Maximize the setting on the reset dial.

7.

Open the manual control valves that are up

stream and downstream, at the same time close

by-pass valves.

8.

Set the controller near the desired control point.

When it reaches that point, begin to narrow

the proportional band until a cycling condition

exists. Broaden the band slightly until a stable

condition is reached. There is no need

to reset the zero in controllers that have reset.

9.

Try to obtain the fastest reset time without intro

ducing cycling control carefully by adjusting the

reset rate.

10.

Test the bandwidth and the reset rate by chang-

ing the pressure setting adjustment for

a moment. If this causes cycling, then broaden

the proportional band and test again. This

procedure is to be repeated until stability is

reached.

The goal for the controller setting is to have the narrow-

est proportional band and the fastest reset rate that will

not cause cycling.

Changing Controller Action

One advantage of the Mark 4150/4160 is the ease at

which you can change from one mode of control to an-

other. There is a connection for both direct and reverse

action in all modes of control. There is also a screw (key

5, figure 6) provided to plug the hole opposite of the

nozzle. It will be necessary to follow INITIAL SETTINGS

after any change in mode of control.

Adjustments

Proportional Band Width Adjustments

The proportional band width adjustment determines the

change in control pressure required to cause the control

valve to travel full open or full closed.

Example:

with the proportional band set @ 1 (10%),

using a Bourdon tube of 0-1000 psi that is set @ 500 psi

on the pressure dial. The full travel of the valve would

occur between 450 psi (3 psi output) and 550 psi (15 psi

output) to try to maintain the set point.

Using this theory, an input pressure of 500 would give

you an output pressure of 9 psi. The greater the propor-

tional band setting is the slower the reaction.

Figure 1: Pressure Connections for

Proportional Controller

Figure 2: Pressure Connections for

Proportional-Reset Controller

Reset Rate Adjustment

By definition the reset rate is the number of minutes that

it takes to adjust the controller to adjust the output pres-

sure up or down by the same amount of proportional

change output caused by the process change.

The reset rate is calibrated in minute per repeat.

M

ark

4150

and

4160 S

erieS

P

reSSure

C

ontrollerS