Calibrate Zero on Proportional Controllers

1.

Depending on the controller type the supply

pressure will be 20 or 35 psi. Attach a suitable

pressure gauge to the output pressure.

2.

Connect the pressure source to the pressure

block and set the proportional bandwidth to 15%

(1.5).

3.

Zero the pressure setting dial.

4.

Raise or lower the nozzle (Key 34, Figure 6)

to get the desired setting of zero as per chart

below. Nylon insert will hold the nozzle in place.

5.

Allow maximum pressure to the measuring ele-

ment. Set the pressure dial to maximum. Output

pressure should comply with the zero setting

column in the following table, if not go to

Note 1.

Control

Action

Output

Range

Supply

Pressure

Zero

Setting

Direct

3-15 psi

20 psi

8-10 psi

Direct

6-30 psi

35 psi

16-20 psi

Reverse

15-3 psi

20 psi

8-10 psi

Reverse

30-6 psi

35 psi

16-20 psi

Calibrate Zero on Proportional- Reset
Controllers

1.

Depending on the controller type the supply

pressure will be 20 or 35 psi. Attach a suitable

pressure gauge to the output pressure.

2.

Connect the pressure source to pressure block

and set the proportional bandwidth to zero.

3.

Set the reset dial to .005 minutes per repeat.

4.

Zero the pressure setting dial.

5.

Raise or lower the nozzle (Key 34, Figure 6) to

get the desired setting of zero as per

chart below. Nylon insert will hold the nozzle in

place.

6.

Allowing maximum pressure to the measuring

element. Set the pressure dial to maximum. Out-

put pressure should comply with the zero setting

column in the following table, if not go to Note 1.

Note 1 -

These steps are to be used if the zero setting

pressure or output range is not obtained when maximum

pressure is applied to the measuring element.

1.

Move the calibration adjuster (Key 30, Figure 6)

to the right or the left.

2.

Repeat the nozzle adjustment and Step 5 for

proportional controller, or Step 6 for proportional-

reset controller.

3.

To release the calibration adjuster, loosen two

screws, above and below the beam, to the left of

the nozzle.

Control

Action

Output

Range

Supply

Pressure

Zero

Setting

Direct

3-15 psi

20 psi

8-10 psi

Direct

6-30 psi

35 psi

16-20 psi

Reverse

15-3 psi

20 psi

8-10 psi

Reverse

30-6 psi

35 psi

16-20 psi

Changing of Controller Output

Controllers having an output range of 3-15 psi, can be

converted to having an output range of 6-30 psi. This

can be done by changing the two color coded control

bellows. The green bellows is for 3-15 range, and yellow

bellows for 6-30 psi range.

When the pressure range is changed, it is necessary to

change the pressure gauges. This can be completed

by unscrewing the old pressure gauges from their boss

and screwing in the new gauges.