0 installation, Inside generator ground, Relay timing for gen type: 2-wire maintain mode – Magnum Energy AGS Network (ME-AGS-N) User Manual

Page 22

Advertising
background image

2.0

Installation

© 2012 Magnum Energy, Inc.

16

Gen

Battery

≤5

amp

fuse

Monitored

battery bank

(12V/24V/48V)

≤5

amp

fuse

Run / Off

Switch

Inside Generator

Ground

≤5

amp

fuse

12/24/48V

ON

4
3
2
1

Gen Type

(2-Wire

Maintain

Mode)

Input DC Voltage

Jumper - set to

monitored battery

bank voltage

(on 24V setting)

Gen

Hour Meter

0 1 2 3

GEN AND POWER I/O

R2

Relay 1

(Terminals 5 & 6)

Delay

Relay 2

(Terminals 6 & 7)

GEN RUN PERIOD

RUN

OFF

Relay timing for Gen Type: 2-Wire Maintain Mode

R2 (Relay 2) Time

Delay time

Time between start attempts

10 sec.

4 sec.

2 min.

Timing Information

Total start attempts

4

Relay 3

(Terminals 1 & 8)

OFF

INSIDE

INSIDE

Connected via

communication cable to

inverter’s Network port

Figure 2-13, Two-wire Control Type Generators