76

10.0 Using the ME-RTR Router

METER: 03A AGS Status Menu
This read-only menu displays the AGS’s current status. There are 26 differ-

ent status messages to identify what state the AGS is currently in – only one

displays at any one time (refer also to Figure 10-2).

METER: 03B DC Volts-AGS Menu
This read-only menu displays the DC voltage measured at Terminals #3 and

#4 of the AGS module. This menu is useful in setting up the voltage start for

the AGS, and for troubleshooting its operation.

Info: The DC voltage reading in this menu may vary from the DC

voltage readings in the METER button’s 01A DC Volts and 04C DC

Volts-BMK menus. When troubleshooting, read the appropriate re-

lated meter for each device. When troubleshooting the AGS, use the

03B DC Volts-AGS menu for verifi cation and testing purposes.

Available statuses are (see Tables 11-1 thru 11-3 for information on each):

Info: This menu is important when determining if the AGS is work-

ing correctly, or for troubleshooting an AGS installation. For any

fault mode displayed in the status menu, refer to Section 12.0 in

this manual.

METER: 03C Gen Run Time Menu
This read-only menu displays the length of time the generator has been

running since it was autostarted by the AGS. This is useful when trying to

determine how long the generator has been running since it was autostarted

– in case you were not present when it started. This menu is enabled when

the CTRL: 03 Gen Control menu is set to AUTO, but does not display run

time when the generator has been manually started. Cooldown and warm-up

times are not included in this gen run time display.

• AC

In

• Gen

Cooldown

• Gen

Warm-up

• Manual

Run

• No

Comm

• Off
• Quiet

Time

• Ready

• Start

Amp

• Start

Exercise

• Start

SOC

• Start

Temp

• Start

Test

• Start

Time

• Start

Topoff

• Start

VDC

Gen Run Fault

• Fault

Amp

• Fault

Exercise

• Fault

MaxRn

• Fault

SOC

• Fault

Temp

• Fault

Test

• Fault

Time

• Fault

Topoff

• Fault

VDC

Info: The Gen Run Time menu’s timer is started when the gen run

sense voltage/signal is correct and qualifi ed at the AGS module. It is

not considered qualifi ed until after a full start attempt and the Gen

Warm-up Time setting is satisfi ed. Cooldown and warm-up times are

not included in the gen run time display. Total generator run time =

Gen Run Time + Gen Warm-up Time + Gen Cooldown.

Info: The times in this display are shown in tenths of an hour (0.0

hrs., 0.1 hrs., etc.,) – thus, 0.1 hrs. = 6 minutes.

Info: The Gen Run Time display resets to 0.0 each time the genera-

tor is autostopped. This meter is not designed to replace the hour

meter for total hours the generator has run.