Setup: 04a gen run vdc menu, 0 using the me-rtr router – Magnum Energy AGS Network (ME-AGS-N) User Manual

Page 68

Advertising
background image

© 2012 Magnum Energy, Inc.

62

10.0 Using the ME-RTR Router

SETUP: 04A Gen Run VDC Menu
This menu starts and stops the generator based on the battery voltage as

shown on the METER button’s 03B DC Volts-AGS menu. This menu provides

the option to start the generator when the battery voltage gets low, and to

stop the generator once the battery reaches a higher voltage level, or has

been fully charged and goes into the Float Charge stage. Using voltage is the

most common method of automatically starting and stopping the generator

because it is considered the simplest and easiest to understand. The 04A

Gen Run VDC menu also has a delay setting to minimize nuisance starts/

stops and the short cycle run times of the generator.
• Set Start Gen Volts – This setting will start the generator when the

battery voltage (on Terminals #3 & #4) decreases to or below this set-

ting continuously for the duration of the Set Start Volts Delay setting.

Autostart Condition Autostop Condition See Setup Menu Page
Starts on low battery

voltage (DC voltage

connected to Termi-

nals #3 and #4)

Stops on higher bat-

tery voltage

04A Gen Run VDC 62

Stops at Float charge

after a set time

period (using Absorb

Done Time setting)

04A Gen Run VDC

(Set Stop Gen

Volts = Float)

62

Stops at Float charge

after battery current

requirement is low

(using Absorb Done

Amps setting)

04A Gen Run VDC

(Set Stop Gen

Volts = Float)

62

Stops at Float charge

using a battery SOC

setting (using Absorb

Done SOC setting)²

04A Gen Run VDC

(Set Stop Gen

Volts = Float)

62

Starts at a set time

daily

Stops at a different

set time daily

04B Gen Run

Time

65

Starts on high AC

amps to an inverter

load¹

Stops on lower AC

amps to an inverter

load¹

04C Gen Run

Amps

65

Starts when the bat-

tery State of Charge
(SOC)²

is low

Stops when the bat-

tery State of Charge
(SOC)²

is higher

04D Gen Run

SOC

66

Starts when temper-

ature increases

Stops after a set

time period

04E Gen Run

Temp

67

Note¹: Only applicable to MS-PAE and MS-PE inverters.
Note²: Autostart/autostop conditions using SOC require the ME-BMK (bat-

tery monitor) to be installed.

Table 10-1, ME-RTR Autostart/Autostop Matrix

Advertising