Description, Instruction manual – Emerson Process Management FISHER 657 User Manual

Page 2

Advertising
background image

Instruction Manual

D100306X012

657 Actuator (30-70 and 87)

December 2010

2

Do not install, operate, or maintain a 657 actuator without being fully trained and qualified in valve, actuator, and
accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is important to
carefully read, understand, and follow all the contents of this manual, including all safety cautions and warnings. If you
have any questions about these instructions, contact your Emerson Process Management sales office before
proceeding.

Table 1. Specifications

SPECIFICATION

(1)

ACTUATOR SIZE

30

34

40

45

46

50

60

70

(1)

87

(1)

Nominal Effective Area

cm

2

297

445

445

677

1006

677

1006

1419

1419

Inch

2

46

69

69

105

156

105

156

220

220

Yoke Boss Diameters

mm

54

54

71

71

71

90

90

90

127

Inches

2‐1/8

2‐1/8

2‐13/16

2‐13/16

2‐13/16

3‐9/16

3‐9/16

3‐9/16

5

Acceptable Valve

Stem Diameters

mm

9.5

9.5

12.7

12.7

12.7

19.1

19.1

19.1

25.4

Inches

3/8

3/8

1/2

1/2

1/2

3/4

3/4

3/4

1

Maximum Allowable

Output Thrust

(4)

N

10230

10230

12010

25131

33582

25131

30246

39142

39142

Lb

2300

2300

2700

5650

7550

5650

6800

8800

8800

Maximum Travel

(2)

mm

19

29

38

51

51

51

51

76

(3)

76

(3)

Inches

0.75

1.125

1.5

2

2

2

2

3

(3)

3

(3)

Maximum Casing

Pressure for

Actuator Sizing

(4)

Bar

8.6

4.5

4.5

3.4

2.8

3.4

2.8

3.8

3.8

Psig

125

65

65

50

40

50

40

55

55

Maximum Diaphragm

Casing Pressure

(4)(5)

Bar

9.6

5.2

5.2

4.1

3.4

4.1

3.4

4.5

4.5

Psig

140

75

75

60

50

60

50

65

65

Material Temperature

Capabilities

_C

Nitrile Elastomers: -40 to 82

_C, Silicone Elastomers: -54 to 149_C, Fluorocarbons: -18 to 149_C

_F

Nitrile Elastomers: -40 to 180

_F, Silicone Elastomers: -65 to 300_F, Fluorocarbons: 0 to 300_F

Pressure Connections

(internal)

1/4 NPT

X

X

X

X

X

X

X

‐ ‐ ‐

‐ ‐ ‐

1/2 NPT

‐ ‐ ‐

‐ ‐ ‐

‐ ‐ ‐

‐ ‐ ‐

‐ ‐ ‐

‐ ‐ ‐

‐ ‐ ‐

X

X

Approximate Weights

kg

16

22

23

37

49

42

53

107

116

Lb

36

48

51

82

107

92

116

235

255

1. These values also apply to the 657‐4 actuator construction.
2. Actuator travel may be less than the value listed after connecting the actuator to the valve.
3. Maximum travel for 657‐4 is 102 mm (4 inches).
4. Normal operating diaphragm pressure must not exceed maximum diaphragm casing pressure and must not produce a force on the actuator stem greater than the maximum allowable out­
put thrust or the maximum allowable valve stem load. Contact your Emerson Process Management sales office with questions concerning maximum allowable valve stem load.
5. This maximum casing pressure is not to be used for normal operating pressure. Its purpose is to allow for typical regulator supply settings and/or relief valve tolerances.

Description

The 657 actuator (figure 1) and the 657‐4 actuator are direct‐acting, spring‐opposed diaphragm actuators. They
provide automatic operation of control valve body assemblies. The 657 actuator offers 76 mm (3 inches) maximum
actuator travel. The 657‐4 actuator provides 102 mm (4 inches) maximum actuator travel. Both actuators position the
valve plug in response to varying pneumatic loading pressure on the actuator diaphragm. Figure 2 shows the
operation of these actuators.

A 657 or 657‐4 actuator can be equipped with either a top‐mounted or a side‐mounted handwheel assembly. A
top‐mounted handwheel assembly is used as an adjustable up travel stop to limit actuator travel in the up direction
(see figure 2). A side‐mounted handwheel assembly is usually used as an auxiliary manual actuator. Adjustable
casing‐mounted up or down travel stops are also available for this actuator.

Advertising