0 technical specifications, 1 conformity and standards, Table 33 environmental characteristics – Emerson Liebert NX 50 and 60 Hz User Manual

Page 127: Echnical, Pecifications, Conformity and standards, Table 31, Compliance with european, international standards, Table 32, Environmental characteristics

Advertising
background image

Technical Specifications

115

10.0 T

ECHNICAL

S

PECIFICATIONS

10.1

Conformity and Standards

The UPS has been designed to conform to the following European and international standards:

The above mentioned product standards incorporate relevant compliance clauses with generic IEC

and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/

AS61000 series) and construction (IEC/EN/AS60146 series and 60529). For more details, see below:

The product standards in Table 32 incorporate relevant compliance clauses with generic IEC and EN

standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000

series) and construction (IEC/EN/AS60146 series and 60529).

Table 32

Compliance with European, international standards

Description

Normative reference

General and safety requirements for UPS used in operator
access areas

EN 50091-1-1 /IEC 62040-1-1 / AS 62040-1-1

Electromagnetic compatibility (EMC) requirements for UPS

EN 50091-2 / IEC 62040-2 / AS 62040-2 (Class A)

Method of specifying the performance and test requirements of
UPS

EN 50091-3 / IEC 62040-3 / AS 62040-3 (VFI
SS 111)

Description

Normative reference

Safety for Information technology equipment

EN60950 / IEC 60950 / AS 60950

Degrees of protection provided by enclosures (IP code).

EN 60529/ IEC60529 / AS 60529

Semiconductor convertors. Part 1: General requirements and line
commutated convertors. Part 1-1: Specifications of basic requirements

IEC 60146-1-1 / AS 60146-1-1

Electromagnetic compatibility (EMC): immunity test

IEC / AS 61000-4-2, -3-4, -5, -6

Limits for harmonic current emission

IEC / AS 61000-3-2, -3-4, -3-6

Table 33

Environmental characteristics

Rated Power, kVA

Unit of

Measurement

30

40

60

80

100

120

140

160

200

Acoustic noise level at 1 meter

dBA

55

55

59

59

62

62

65

65

66

Altitude of Operation

m (ft)

≤1000 (3280) above sea level

derate power by 1% per 100m between 1000 and 2000 (3280-6562)

Relative Humidity

0 to 95% non condensing

Operating Temperature

°C (°F)

0 to 40 (32 to 104)

Note: Battery life is halved for every 10°C increase above 20°C

UPS Storage-Transport Temperature

°C (°F)

-20 to 70 (-4 to 158)

Recommended Battery Storage
Temperature

°C (°F)

-20 to 30 (-4 to 86)

(20 for optimum battery storage)