Single Module UPS Installation

8

1.6

Power Cables

The cable design must comply with the voltages and currents provided in this section, follow local wir-

ing practices and take into consideration the environmental conditions (temperature and physical

support media).
For cable entry terminal, refer to Figures 43, 48, 52 and 56.

!

WARNING

Before starting the UPS, ensure that you are aware of the location and operation of the

external isolators that connect the ups input/bypass supply to the mains distribution panel.
Check that these supplies are electrically isolated and post any necessary warning signs to

prevent their inadvertent operation.

Table 1

Maximum steady state AC and DC currents

UPS

RATING

(kVA)

NOMINAL CURRENT: Amps

BUSBAR STUD SIZE

Input Mains

with full battery

recharge

3ph + N

Bypass/Output

at full load

3ph + N

Battery at

minimum

battery

voltage

(400VDC)

Input/Output/

Bypass
Cables

Battery

Cables

(Bolts)

Torque

Load, Nm

(lb/ft)

380V

400V

415V

380V

400V

415V

Bolt

Ø holes

30

50

47

45

46

43

42

64

M6

7

-

5 (1.12)

40

65

62

60

61

58

56

85

60

97

92

88

91

86

83

128

M8

9

M10 Ø11

M8: 13 (2.9)

M10: 26 (5.8)

80

128

122

117

121

115

111

170

100

160

152

146

152

145

139

213

M10

11

120

191

181

175

182

174

167

255

140

222

211

204

212

201

194

298

160

254

241

232

242

230

222

340

200

317

301

290

303

288

277

426

For terminal location – refer to 5.0 - Installation Drawings

Table 2

Distance from floor to connection point on the equipment

UPS

Minimum Distance, mm (in)

UPS 30/40 kVA

UPS 60-80 kVA

UPS 100-120 kVA

UPS 140-200 kVA

Rectifier AC Input supply

350 (13.8)

305 (12)

324 (12.8)

Bypass AC Input supply

300 (11.8)

250 (9.8)

310 (12.2)

UPS Output AC

260 (10.2)

250 (9.8)

310 (12.2)

Battery Power

1030 (40.5)

230 (9)

360 (14.2)

Auxiliary cables:
Monitor board (U2)

1320(52)

1500 (59)

Communications

1070(42.1)

1250(49.2)

Earth

350 (13.8)

275 (10.8)

338 (13.3)

!

WARNING

Failure to follow adequate earthing procedures may result in electromagnetic interference or

in hazards involving electric shock and fire.