6.1

Introduction

The Liebert NXa Uninterruptible Power System is connected between the Mains AC input source and

the critical load to provide uninterruptible power to the latter. The power from the UPS is free from

voltage and frequency variations and from disturbances experienced at the Mains AC input supply.

This is achieved through high frequency double conversion power pulse width modulation (PWM)

associated with full digital signal processing control (DSP).
As shown in Figure 63, the AC input mains source is supplied at Q1 and converted into a DC source.

This DC source feeds a DC/DC Bidirectional Battery Converter (that ensures the battery to remain

charged at all times) and at the same time feeds the Inverter that converts the DC source into a clean

and input independent AC source. The battery powers the load through the bidirectional battery con-

verter and through the inverter in case of an AC input mains power failure. In case of Inverter

unavailability or excessive overload, the load may also be powered from an external AC Bypass source

through input isolator Q2 and the static bypass. Besides this, if maintenance or repair of the UPS is

necessary, the UPS can support the load through the internal and manually controlled maintenance

bypass isolator Q3. With the exception of the maintenance bypass isolator, all the isolators shown are

closed during normal UPS operation.

Figure 63 Single unit block diagram with split-bypass input

!

WARNING

Hazardous mains and / or battery voltage present behind covers.
No user-serviceable parts are located behind covers that require a tool for their removal. Only

qualified service personnel are authorised to remove such covers.

1

Battery

Circuit

Breaker

2

Battery

UPS

Output

Battery

Converter

Input

Static

Switch

Input

Isolator

Q1

Rectifier

Inverter

Static Switch

Output

Isolator

Q5

DC Bus

Bypass Isolator Q 2

Maintenance Bypass Isolator Q 3

UPS Module

Bypass

Mains

Supply

Input

Mains

Supply

N

Bypass Side

CB