Troubleshooting

32

Assert manual

bypass

A user-initiated transfer to bypass will

assert this alarm, instructing the user to

enable the manual bypass switch. Once

the manual bypass is asserted, the alarm

will clear. This is a non-mutable alarm.

Engage the manual bypass switch (located at the bottom

front on the left hand corner of the unit). Once engaged,

the switch may be de-asserted to return to normal

operation.

Remote shutdown

on COM port 1

active

The most likely cause is that the incorrect

cable has been connected to the COM

port between the UPS and the host.

Check for a wiring problem to the Shutdown On Battery at

the COM1 connector. If this problem is not addressed, the

unit will shut down shortly after switching to battery

operation.

Battery Test

Weak Battery

The battery was determined to be weak

as a result of the battery test.

Depending on the age of the batteries, it may be

appropriate to replace all batteries in the system.

Schedule a battery test so that the system operation is

double-checked once the batteries become fully charged.

Battery Test

Failure

One or more of the following was

detected during a battery test:

• UPS output regulation failure was

detected.

• A battery module warning or failure

occurred.

• A system control failure occurred.

Replace the battery modules that have active failures/

warnings. Depending on the age of the batteries, it may be

appropriate to replace all batteries in the system.

Schedule a battery test so that the system operation is

double-checked once the batteries become fully charged.

Battery Cabinet

Not Connected

This is intended to detect a situation

where a Modular battery cabinet has

been connected for communication, but

the power busses are not connected.

Check that the Modular Battery breaker is closed. Verify

proper connections between UPS and Modular Battery

Cabinet.

Don’t Remove SC

The only good System Control Module

lock lever was raised with the output on

and the unit is not on bypass.

• Lower the lock lever on the System Control Module.

• Provide qualified bypass power so that transfer to

bypass is possible.

• Add a redundant System Control Module so that the load

is not dropped.

Failure: Select

Manual Bypass

The System Controller detected a failure.

Select manual bypass so that the unit can

be serviced.

Transfer UPS to manual bypass and contact Liebert

Global Services.

Output Off -

bypass unavailable

This event informs the user that bypass

was not qualified so the unit dropped the

load to protect itself.

Verify that the UPS’s bypass source is qualified (amplitude

and frequency). Verify that the configuration voltage and

frequency settings are properly selected.

Last UPS Shutdown

By Emergency

Power Off

REPO switch was pressed.

If REPO wasn’t pressed, check for REPO wiring problems.

External Battery

Module Warning

The energy delivered from the Non-

Modular battery did not meet

programmed battery capacity.

Verify proper connections between UPS and Non-Modular

Battery Cabinet. Reenter the amp-hour rating for the

external battery (set the amp-hour entry to zero and press

the return key, then reset it to the appropriate value for the

external battery). If the problem persists, the external

battery should be replaced.

Battery Module

Not Ready

A battery module is not ready. In most

cases, one or more battery modules

should indicate a warning/failure

condition.

Ensure that the battery module is fully seated and the 1/4

turn fastener is engaged. If the problem persists, replace

the battery module with warning/failure condition indicated

at the User Interface. If no User Interface warning/failure

of battery module, look for the battery module with LEDs

indicating a problem and replace that unit.

Power Module

Not Ready

A power module is not ready. In most

cases, one or more power modules

should indicate a warning or failure

condition.

Ensure that the power module is fully seated and the 1/4

turn fastener is engaged. If the problem persists, replace

the power module with warning/failure condition indicated

at the User Interface. If no User Interface warning/failure

of power module, look for the power module with LEDs

indicating a problem and replace that unit.