0 specifications, 1 product warranty registration, Pecifications – Emerson Nfinity 208 User Manual

Page 41: Product warranty registration

Advertising
background image

Specifications

37

6.0

S

PECIFICATIONS

6.1

Product Warranty Registration

To register for warranty protection:

• Visit the Quick Links section of our Web site at:

http://www.liebert.com

• Click on Product Warranty Registration and fill in the form.

If you have any questions, please contact us at:

US: 800-222-5877

Outside the US: 614-841-6755

[email protected]

General & Environmental

Units

Configuration

Unit Rating

k

VA

12

16

20

20

k

W

8.4

11.2

14

16

Conducted and Radiated EMC Levels

FCC Part 15, Class A

Compliant Safety Standards

UL 1778; c-UL

Compliant Immunity Standards

IEEE C62.41, Category B

Mechanical

Units

Dimensions

Width

in (mm)

20 (508)

Depth

28 (711)

Height

54 (1372)

Environmental

Units

Operating Temperature (max)

C (F)

0° - 40° (32° - 104°)

Relative Humidity

%

0-95% non-condensing

Maximum operating altitude

M (ft.)

3,000 (10,000)

Nominal heat dissipation

BTU/Hr

3,186

4,248

5,903

6,748

Acoustic noise level

dBA

<62 @ 1 meter

Input Data

Units

Nominal input voltage

VAC

208 or 240

Voltage Range (Typical)

208VAC nominal: operating voltage range variable based on output loading percentages

% UPS Load

Input Voltage

80 – 100%

170 VAC

60 – 80%

144 VAC

30 – 60%

127 VAC

0 – 30%

110 VAC

Power factor

Cos

>.98

Input frequency (nominal)

Hz

60

Input frequency range

Hz

40-70

Battery Module

Units

Number of lead acid batteries

10

Number of battery cells

60

Battery capacity

A/hr

9

Autonomy time (full load)

minutes 6 (With an equal number of Battery & Power Modules, in a non-redundant configuration)

Maximum charge current (full load)

A

3

Nominal Voltage

VDC

120

Recharge Time

Hrs

Typically 6 (to 90% capacity)

Output Data

Units

Output voltage

VAC

208/120 or 240/120

Voltage regulation

%

±3

Voltage stability (100% step load)

%

±7

Recovery time

msec

96

Voltage distortion

%

<3 THD, linear load

<7 THD, non-linear load

Output frequency

Hz

60

Efficiency at 100% load

%

89

Output overload capability

%

110 - 125% for 10 min

126-150% for 10 sec

151 - 200% for 2 cycles

Advertising
This manual is related to the following products: