Installation

13

2.3.2 Connecting to External Panel Boards

The following instructions are also shipped attached to the rear of the unit.

INPUT CABLING AND PROTECTION

Table Below Applies to 12-20kVA Scalable Systems:

Stand-alone UPS or
UPS equipped with a Maintenance Bypass Cabinet (Without Transformer)

UPS With Maintenance Bypass Cabinet (With Transformer)

Single Input Feed: All UPS ratings must use 125A input circuit breaker protection.
Dual Input Feed: See table below.

Bypass Voltage Jumper Position (TB2)

Max. System

Load Rating

Input Voltage – 208VAC

Input Voltage – 240VAC

Max. Current

in UPS mode

Recommended

Input Protection

Circuit Breaker

Max. Current

in UPS mode

Recommended

Input Protection

Circuit Breaker

12kVA

53 amps

75 amps

46 amps

75 amps

16kVA

70 amps

100 amps

62 amps

100 amps

20kVA

102 amps

125 amps*

88 amps

125 amps*

Terminal

Block

Details

Maximum: 35mm

2

(2AWG) * Must use 90° copper wire

Minimum: 16mm

2

(6AWG)

Torque Rating: 2.5-3.0Nm (22-26in/lbs)

Max. System

Load Rating

UPS Feed

Bypass Feed

Input Voltage – 208VAC

Input Voltage – 240VAC

208V or 240V

Max. Current
in UPS mode

Recommended

Input Protection

Circuit Breaker

Max. Current

in UPS mode

Recommended Input

Protection Circuit Breaker

Recommended

Input Protection

Circuit Breaker

12kVA

53 amps

75 amps

46 amps

75 amps

125 amps*

16kVA

70 amps

100 amps

62 amps

100 amps

125 amps*

20kVA

102 amps

125 amps*

88 amps

125 amps*

125 amps*

Terminal

Block

Details

Maximum: 35mm

2

(2AWG) * Must use 90° copper wire

Minimum: 16mm

2

(6AWG)

Torque Rating: 2.5-3.0Nm (22-26in/lbs)

Bypass Voltage Selection

208 VAC

(Factory Default)

240 VAC

(Field Change)

Jumper/link

on upper two

screws

Jumper/link

on lower two

screws