Operating Instructions

19

3.4

Operating Procedures

3.4.1 Start-Up and Initialization

Follow these steps to start up the UPS.
1. Ensure the manual bypass switch is in

UPS position. Close Input Circuit Breaker

(CB1) and close the Control Enable

Switch (SW2). You should see the

following on the LCD display window:

2. Press

or

button.

3. Press

to access the Main Menu.

3.4.2 Shutting Down the UPS

Use the following procedure to power down

the UPS.
1. Press

to disable power from the

connected equipment.

2. Verify request to disable the output by

pressing .

3. Turn off the Enable Switch (SW2). Open

the Input Circuit Breaker (CB1).

3.4.3 Manual Transfer to Bypass

To manually transfer the UPS to bypass,

move the manual bypass switch to the bypass

position. The manual bypass switch is behind

the front bottom bezel. To transfer the UPS

from bypass to normal mode, follow the on-

screen instructions.

Once

is pressed, the bypass alarm will

annunciate and cannot be canceled until the

manual bypass switch is operated.

To transfer the UPS from bypass to normal

mode, simply operate the manual bypass

switch back to the UPS position.
On return from bypass, the following screen

will be displayed.

UPS Initializing

Please wait . . .

*Press

to Enable

UPS Output.

ESC

On Mains/Utility
Output % = xx
Battery Minutes yyy
Press

for menu

NOTE
The load is not protected from utility

interruptions when the UPS is in

bypass mode.

Main Menu

> Transfer to Bypass

Transfer to Bypass

Press

for bypass

Press ESC to cancel

Assert manual bypass

Manual

Bypass

Switch

On UPS

On Bypass

UPS on manual bypass

No active alarms
See Event Log